| Primary Power |
| 120 - 220VAC + 10% - 15%, 60 / 50 Hz, |
| Standby Power |
| 24v D.C (2 Nos of 12v, 14Ah Sealed Lead acid battery). |
| Operating Condition |
| Operating Temperature 0-49° C/32-120°
F. Relative Humidity 93±2% RH (non-condensing)
at 32 ±2° C/96 ±30 F.
|
| Charging Circuit |
| Charging Voltage 28.4V, ±0.2V Nominal
Charging Current 1.2A (Max.).
|
| Signaling Line Circuits |
| Class A or B loop Card: 4 Nos Maximum Number of
Device per loop: Multi protocol for Devices
Number of Device per loop: 254 Devices per Loop
Loop resistance: 40 ohms (Max.).Loop Capacitance: 06
µf (Max.). Loop Current:
250mA (Max.). |
| Initiating Device Circuits |
| All zones are Class B Style B/C operation (Programmable).
Normal Operating Voltage : 14-21 VDC.
Alarm Current : 15- 30mA.
Short Circuit Current : 45mA Maximum
Loop resistance : 100 ohms MaximumEnd-Of-Line Resistor
: 4k7, 1/2watt
Standby Current : 7mA (2mA for Detectors) |
| Notification Appliance Circuits |
| Class B Style - Y wiring
Operating Nominal Voltage : 24VDC Nominal
Current for NACs: 1Amps
Line Drop: 2.4V
End-Of-Line Resistor: 4K7, 1/2watt |
| D.C. Output |
| Supervised 24VDC, 300mA Max.
|
| 3 Common Three Form C Relays |
| Relay Contact Rating : 2Amps @ 30 VDC. 2Amps @ 3OVAC.
Power Factor : 0.6
|