RE 101FI

Features:
Dedicated
I Zone Fire and 1 zone Intruder.
Battery
backup with built-in charging.
Fire
I Fault status in unambiguous colored LED indication.
Arm
& Disarm Facility for the Intruder.
Intruder
Status (Alarm) Indication.
Low
battery audio I visual warning.
Charger
ON indication.
A.C
fail audio I visual warning.
Zone
Isolation facility with loop voltage cut off.
24v
DC output for external notification devices. [Sounders, etc.,]
Fire,
Fault & Intruder Potential Free Contacts.
User,
Installer & Maintenance friendly.
Technical Specification :
|
AC Power
Supply |
230V AC,5OHz
|
|
Standby
Supply |
24V DC
|
|
Operating
Condition |
-10 to 45 0C
, 30-95% RH. |
|
Operating
Voltage |
24V DC |
|
Normal Loop
Voltage |
20.7V DC |
|
Open
Threshold Current |
4.2 mA. |
|
Short
Circuit Threshold Current |
40 mA.
|
|
Stand by
Threshold Current |
8.2 mA (EOL
Current + Detector’s
Current) |
|
Alarm
Current |
20-35 mA |
|
Quiescent
Current |
30 mA +
4.2mA I Zone |
|
Standard
Common Souder Output |
500mA max.
|
|
External DC
Output |
500mA Max.
|
|
Potential
Free Relay Contacts |
2A @ 230V |
|
Arm liming |
20sec.
|
Download user manual
Download
Data Sheet
|