RE 101G

Features:
Dedicated
2 Zones with Cross Zone facility.
Battery
backup with built-in charging.
Fire
I Fault status in unambiguous coloured LED indication.
Low
battery audio I visual warning.
Charger
ON indication.
A.C
fail audio I visual warning,
Output
for remote repeater panel.
Zone
Isolation facility with loop voltage cut off.
Auto
I Manual mode facility.
External
and Internal Gas Release & Inhibit Switch facility.
Programmable
Timer for gas release.
User,
Installer & Maintenance fhendly.
24v
DC output for external notification devices.[Sounders, etc.,]
Common
Fire & Fault Potential Free Contacts.
Technical
Specification :
|
AC Power
Supply |
230V AC 50Hz
|
|
Standby
Supply |
24V DC |
|
Operating
Condition |
-10 to 45 °C
, 30-95% RH. 24VDC |
|
Operating
Voltage |
24V DC |
|
Normal Loop
Voltage |
20.7V DC |
|
Open
Threshold Current |
4.2 mA.
|
|
Short
Circuit Threshold Current |
40 mA |
|
Stand by
Threshold Current |
8.2 mA (EOL
Current + Detectors Current) |
|
Alarm
Current |
20 - 35 mA
|
|
Quiescent
Current |
30 mA +
4.2mA I Zone |
|
Standard
Common Souder Output |
500mA max. |
|
External DC
Output |
500mA Max. |
|
Potential
Free Relay Contacts |
2A @ 230V
|
Standard Common Sounder Output : .
0.2mA / zone
Download user manual