RE 101H

Features:
Dedicated
2 Zones.
Battery
backup with built-in charging.
Fire
/ Fault status in unambiguous coloured LED indication.
Low
battery audio I visual warning.
Charger
ON indication.
A.C
fail audio I visual warning.
Output
for remote repeater panel.
Zone
Isolation facility with loop voltage cut off.
User,
Installer & Maintenance friendly.
24v
DC output for external notification devices.[Sounders, etc.,]
Technical
Specification :
|
AC
Power Supply |
230V
AC,5OHz |
|
Standby Supply |
24V DC |
|
Operating Condition |
-10 to
45°C 30-95% RH. |
|
Operating Voltage |
24V DC |
|
Normal
Loop Voltage |
20.7V
DC |
|
Open
Threshold Current |
4.2 mA. |
|
Short
Circuit Threshold Current |
40 mA. |
|
Stand
by Threshold Current |
8.2 mA
(EOL Current + Detector’s) |
|
Alarm
Current |
20-35
mA |
|
Quiescent Current |
30 mA
+ 4.2rnA I Zone |
|
Standard
Common Souder Output |
500mA max. |
|
External DC Output |
500mA Max. |
|
Potenal Free
Relay Contacts |
2A@230V |
Standard Common Sounder Output : .
0.2mA / zone