Conventional Panels >> RE 104

Features:
Rugged
CRCA sheet with powder coated finish.
Operates
on 220v, 50Hz AC supply.
Standby
battery back up with built in charging.
Fire
/ Fault status in unambiguous colored LED indication.
Switch
Mode Power Supply.
Tactile
key pad for easy panel operation.
System
on indication.
Main,
Standby status indication.
Low
Battery visual warning with audible tone.
Relay
output for actuators for Fire and Fault.
Lamp
Test facility.
Zone
wise one man Walk Test facility.
Zone
wise Isolation facility with loop voltage cut off.
Compatible
to all types of conventional detectors.
Technical Data :
|
Power Supply
|
|
AC Input Supply
|
220 VAC, 50Hz
|
|
DC Input Supply
|
24V DC
|
|
Operating Conditions
|
-10 to 45 C,
95 % RH Max.
|
|
Operating Voltage
|
24 V DC
|
|
Normal Loop
Voltage
|
20.7 DC
|
|
Open Threshold
Current
|
4.2 mA
|
|
Short Circuit
Threshold Current
|
40 mA
|
|
Stand by Threshold
Current
( EOL Current
+ detector's Current)
|
8.2 mA
|
|
Alarm Current
|
20 - 35 mA
|
|
Quiescent Current
|
60mA
|
|
Colour of the
Panel
|
Broken White
(Red, Red Texure - Optional)
|
|
Dimension of
the Panel
|
350 x 250 x
100 mm (W x h x d)
|
|
Approximate
Weight
|
4Kgs.
|
|
ALARM OUTPUT
|
|
Common Hooter
Output
|
24V@1A.
|
|
REMOTE OUTPUTS
|
|
Outputs
|
Fire, Fault
Relay Contacts (30V AC/ DC @ 2A contact).
|
|