| Power |
| Power |
220-240 VAC, 50 Hz. |
| Wire size |
1.5 Sq. mm with 600V insulation |
| Battery (Lead Acid only)
|
| Charging Voltage |
27.9 VDC. |
| Charging Capacity |
7 Amp Hour Battery Max. |
| System Quiescent Current |
80mA + (2.4mA for Detectors) |
| Initiating Device
Circuits (Zone Circuit) |
| |
All zones are Class B wiring |
| Normal Operating Voltage |
Nominal 24 VDC |
| Alarm Current |
15 35mA threshold |
| Short Circuit Current |
40mA Maximum |
| Loop resistance |
50 ohms Maximum |
| End-Of-Line Resistor |
4.7K, 1/4watt |
| Standby Current |
6.8mA (2.4mA for Detectors) |
| Notification Appliance Circuits
(Sounder/Hooter Circuit) |
| Operating Nominal Voltage |
24 VDC |
| Hooter (NACs) output |
0.5A (Each) |
| End-Of-Line Resistor |
47K. 1/4watt |
| Solenoid Relay Output Circuits
|
| Operating Nominal Voltage |
24 VDC |
| Solenoid output |
0.75A (Each) |
| 2No’s of Hooter (NACs) output |
0.3A (Each) |
| End-Of-Line Resistor |
4.7K, 1/4watt (for Solenoid Output) |
| Remote Outputs |
| Fire Contact (C, NO, NC) |
220v AC/30v DC@ 1 A |
| Fault Contact (C, NO, NC) |
220v AC/30v DC@ 1A |
| Timer Contact (C. NO, NC) |
220v AC/30v DC@ 1 A |
| 24 VDC Power For remote devices
(Optional)
|
| Operating Voltage |
24VDC, 500mA Max. |
| RS 24 VDC Power For Four Wire
devices (Optional) |
| Operating Voltage |
24VDC, 500mA Max. |
| Dimension of the Panel |
| Dimension of the Panel |
400 x 300 x 100 mm (l x h x D) |