RE 150D

Features:


Fully confirms IS 2189: 1988

16SWG Rugged CRCA with powder coated finish.

Modular construction.

Operates on 230V, A.C supply.

Battery backup with built in charging.

16x2 LCD Dot matrix Display.

Fire / Fault status in unambiguous coloured LED indication.

Low battery / battery fail warning audio / visual indication.

A.C fail audio / visual warning.

Charger fail audio / visual warning

System on, AC on, Battery on & Charger on indications

Potential Free Relay Contacts for actuators.

Lamp test facility.

One man walk test facility.

Compatible to all types of conventional detectors.

Twin RED LED indication for fire.

Zone Isolation facility with loop voltage cut off.

Earth Fault with Audio and Visual Indications.

Loop Sounder facility.

Supervised Sounder 24v DC output for External notification

devices (Sounder, Bell, etc.).

TECHNICAL DATA

Technical Specification :



AC Power Supply

230V AC,50Hz

Standby Supply

24V DC

Operating Condition

-10 to °49 C , 30-95% RH

Operating Voltage

24V DC

Normal Loop Voltage

20.7V DC

Open Threshold Current

4.2 mA.

Short Circuit Threshold Current

40 mA.

Standby Threshold Current

8.2 mA (EOL Current + Detector's Current)

Alarm Current

20 - 35 mA

Quiescent Current

50 mA + 4.2mA / Zone

Standard Common Sounder Output :  0.2mA / zone