RE 1ZM

Features:

............................................................................................................................................................................................................................................................................
  • Operates on 24 VDC.
  • Communication Status Indication Facility.
  • With / Without Built-in MC?
  • Fire / Fault status in unambiguous coloured LED indication.
  • Compatible to all types of conventional detectors.
  • 24 V DC output for External notification devices (Sounder, Bell, etc.).

Ordering Information:

............................................................................................................................................................................................................................................................................
  • RE 1Z - Single Zone Module
  • RE 1ZM - Single Zone Module with MCP

Technical Specification:

............................................................................................................................................................................................................................................................................
DC Supply 24 V DC
Operating Conditions -10 to 49° C, 30 - 95 % RH
Operating Voltage 24 V DC
Normal Loop Voltage 20.7 DC
Open Threshold Current 4.2 mA
Short Circuit Threshold Current 40 mA
Stand by Threshold Current 8.2 mA ( EOL Current + detector’s Current)
Alarm Current 20 - 35 mA
Quiescent Current 60 mA
Sounder Outputs
Standard Common Output 200mA.