| Primary Power – CN1 (RE-SMPS-4A-R1) |
| 120 - 220VAC ± 10%, 50 Hz, |
| Standby Power – CN10 |
| 24v D.C (2 Nos of 12v, 12Ah Sealed Lead acid battery).
|
| Operating Condition |
| Operating Temperature – 0 - 49° C/32-120° F. Relative
Humidity – 93±2% RH (non-condensing) at 32 ±2° C/90±3° F.
|
| Charging Circuit |
| Charging Voltage – 28.2V, ±0.5V Charging Current –
800mA (Max.).
|
| Initiating Device Circuits - CN 8 |
| All zones are Class B Style B/C operation (Programmable).
Normal Operating Voltage : 14-21 VDC.
Alarm Current : 15- 30mA.
Short Circuit Current : 45mA Maximum
Loop resistance : 100 ohms MaximumEnd-Of-Line Resistor
: 3K9, 1/2watt
Standby Current : 7mA (2mA for Detectors) |
| Notification Appliance Circuits |
| Class B Style - Y wiring
Operating Nominal Voltage : 24VDC Special Application
Current for all NACs : 1.2Amps (0.6A per circuit)Current
Limit: CN5 and CN6 via Thermal Fuse
Line Drop : 1.8V
End-Of-Line Resistor : 3K9, 1/2watt
Note: For compatible devices refer Chapter 9(CD 01).
|
| D.C. Power - CN7 |
| Operating Voltage: Supervised 24VDC regulated. 300mA
Max. (for 4 wire smoke detector) |
| Common Three Form C Relays |
| Relay Contact Rating: 2Amps @ 30 VDC. 2Amps @ 3OVAC.
Power Factor: 0.6
|
| Dimension of the panel |
| 440 x 340 x120mm (l x h x d) |