RE 700

Features:
20
x 4 LCD Dot Matrix display.
Fully
confirms IS 2189: 1988
Rugged
CRCA with powder coated finish.
Operates
on 230V, A.C supply.
Battery
backup with built in charging.
Error
free fire / fault status in unambiguous coloured LED indication
.
20
X 4 LCD Dot Matrix display.
Low
battery / warning audio/ visual display.
Battery
fail warning audio
Charger
on indication.
A.C
fail audio / visual warning.
Relay
output for actuators.
2
to 2 55 Zones Max. (4,8,12,24 Zone Slave Panels).
RS485
for repeater/slave communication (Use shielded or twisted wire
(CAT5E or CAT6)).
Slave Panel Isolation facility.
Real
time clock facility.
Events
of fire and fault can be seen.
RS
232 facility (Optional).
Technical Specification :
|
AC Power
Supply |
230V AC,50Hz
|
|
Standby
Supply |
24V DC
|
|
Operating
Condition |
-10 to 45 oC
, 30-95% RH |
|
Operating
Voltage |
24V DC
|
|
Normal Loop
Voltage |
20.7V DC
|
|
Open
Threshold Current |
4.2 mA.
|
|
Short
Circuit Threshold Current |
40 mA. |
|
Standby
Threshold Current |
8.2 mA (EOL
Current + Detector's Current) |
|
Alarm
Current |
20 - 35 mA
|
|
Quiescent
Current |
70 mA +
4.2mA / Zone |
Standard Common Sounder Output : .
0.2mA / zone
Download user manual